消防水泵控制閥的使用保養要注意什么!
來(lái)源:http://m.guizhouhuli.net/ 日期:2022-03-04
1、每日檢查消防水泵控制閥保養部分,要求控制部分完好;泵組密封情況,消防水泵控制閥投入運行前每秒滴水不超過(guò)一滴。
1. Check the maintenance part of the control valve of the fire pump every day, and the control part is required to be intact; The sealing condition of the pump set, and the water drop per second shall not exceed one drop before the control valve of the fire pump is put into operation.
保養內容:
Maintenance contents:
1、每周消防水泵控制閥保養起碼運行一次,運行時(shí)間電動(dòng)泵不少于10min、柴油泵啟動(dòng)不少于30min,檢查水泵出水壓力是否符合要求。
1. The control valve of the fire pump shall be maintained and operated at least once a week. The operation time of the electric pump shall not be less than 10min and that of the diesel pump shall not be less than 30min. Check whether the outlet pressure of the water pump meets the requirements.
2、每周消防水泵控制閥運行前,檢查泵組是否完好。好比說(shuō),泵的吸水、出手、旁通管能全部開(kāi)放;泵組無(wú)泄漏;進(jìn)、出管壓力表正常;消防水池儲滿(mǎn)消防用水細節問(wèn)題。
2. Check whether the pump set is in good condition every week before the operation of the fire pump control valve. For example, the suction, hand and bypass pipes of the pump can be fully opened; The pump set has no leakage; Inlet and outlet pressure gauges are normal; Details of fire water tank full of fire water.

3、消防水泵控制閥運行前,檢查電器控制部分是否完好。好比說(shuō)電源開(kāi)關(guān)指示正指示燈正常;切換、轉換指示燈正常;備電啟動(dòng)、隔離開(kāi)關(guān)關(guān)閉;報警反饋信號指示燈不亮、正常指示燈開(kāi)啟等細節問(wèn)題。
3. Before the fire pump control valve is operated, check whether the electrical control part is intact. For example, the positive indicator light of the power switch is normal; Switching and switching indicators are normal; Standby power start and disconnector close; The alarm feedback signal indicator is not on, and the normal indicator is on.
4、檢查主、備電源切換正常,檢查備用電源,看能否確保在30s內使水泵投入正常運行;檢測備用水泵能否自動(dòng)切換投入運行。
4. Check whether the switching between main and standby power supply is normal and whether the standby power supply can ensure the normal operation of the water pump within 30s; Check whether the standby water pump can be automatically switched and put into operation.
保養工作:
Maintenance work:
1、定期檢查消防水泵控制閥保養出水管路上閘閥、止回閥、水錘裝置是否正常。
1. Regularly check whether the gate valve, check valve and water hammer elimination device on the outlet pipe of the fire pump control valve maintenance are normal.
2、定期吸水管入口處雜物,防止堵塞。如若消防泵所處環(huán)境衛生條件優(yōu)良,可2-3月檢查一次雜物。
2. Regularly remove sundries at the inlet of the suction pipe to prevent blockage. If the environmental sanitation condition of the fire pump is good, the sundries can be checked once in February to March.
3、打開(kāi)末端試水裝置或消火栓放水,檢查消防水泵控制閥能否正常啟動(dòng),以此確保消防泵使用時(shí)水泵能正常工作。
3. Open the end water test device or fire hydrant to discharge water, and check whether the control valve of the fire pump can be started normally, so as to ensure that the water pump can work normally when the fire pump is used.
在消防水泵控制閥運行前,應由操作人員進(jìn)行監督,以免發(fā)生事故。
Before the operation of the fire pump control valve, the operator shall supervise it to avoid accidents.
長(cháng)期運行后,由于機械磨損,設備的噪音和振動(dòng)會(huì )增加。應該停止并檢查它。有必要更換易損部件和軸承。該泵的大修周期通常為一年。
After long-term operation, the noise and vibration of the equipment will increase due to mechanical wear. It should be stopped and checked. It is necessary to replace vulnerable parts and bearings. The overhaul cycle of the pump is usually one year.
Sichuan consumer has focused on the industry for many years and served customers wholeheartedly. Your satisfaction is our development. For details, click: http://m.guizhouhuli.net