川消室內消火栓的安裝注意事項
來(lái)源:http://m.guizhouhuli.net/ 日期:2023-07-13
1、室內消火栓應設在明顯易于取用地點(diǎn)。栓口離地面高度為1.1m,其出水方向宜向下或與設置消火栓的墻面成90°角;
1. Indoor fire hydrants should be located in clearly accessible locations. The height of the hydrant mouth from the ground is 1.1m, and its water outlet direction should be downward or at a 90 ° angle with the wall where the fire hydrant is installed;
2、冷庫的室內消火栓應設在常溫穿堂或樓梯間內;
2. Indoor fire hydrants in cold storage should be located in room temperature corridors or stairwells;
3、
川消室內消火栓的間距應由計算確定。高層工業(yè)建筑,高架庫房,甲、乙類(lèi)廠(chǎng)房,室內消火栓的間距不應超過(guò)30m;其他單層和多層建筑室內消火栓的間距不應超過(guò)50m。同一建筑物內應采用統一規格的消火栓、水槍和水帶。每根水帶的長(cháng)度不應超過(guò)25m;
3. The spacing of indoor fire hydrants for Sichuan Xiaoxiao should be determined by calculation. The spacing between indoor fire hydrants in high-rise industrial buildings, elevated warehouses, Class A and Class B factories should not exceed 30m; The spacing between indoor fire hydrants in other single-story and multi-story buildings should not exceed 50m. Unified specifications of fire hydrants, water guns, and hoses should be used within the same building. The length of each water hose should not exceed 25m;
4、設有室內消火栓的建筑,如為平屋頂時(shí),宜在平屋頂上設置試驗和檢查用的消火栓;
4. For buildings with indoor fire hydrants, if they are Flat roof, they should be equipped with fire hydrants for test and inspection on Flat roof;

此外還要注意:
Also note:
1、室內消火栓應設在明顯易于取用地點(diǎn)。栓口離地面高度為1.1m,其出水方向宜向下或與設置消火栓的墻面成90°角;
1. Indoor fire hydrants should be located in clearly accessible locations. The height of the hydrant mouth from the ground is 1.1m, and its water outlet direction should be downward or at a 90 ° angle with the wall where the fire hydrant is installed;
2、冷庫的室內消火栓應設在常溫穿堂或樓梯間內;
2. Indoor fire hydrants in cold storage should be located in room temperature corridors or stairwells;
3、室內消火栓的間距應由計算確定。高層工業(yè)建筑,高架庫房,甲、乙類(lèi)廠(chǎng)房,室內消火栓的間距不應超過(guò)30m;其他單層和多層建筑室內消火栓的間距不應超過(guò)50m。同一建筑物內應采用統一規格的消火栓、水槍和水帶。每根水帶的長(cháng)度不應超過(guò)25m;
3. The spacing of indoor fire hydrants should be determined by calculation. The spacing between indoor fire hydrants in high-rise industrial buildings, elevated warehouses, Class A and Class B factories should not exceed 30m; The spacing between indoor fire hydrants in other single-story and multi-story buildings should not exceed 50m. Unified specifications of fire hydrants, water guns, and hoses should be used within the same building. The length of each water hose should not exceed 25m;
4、設有室內消火栓的建筑,如為平屋頂時(shí),宜在平屋頂上設置試驗和檢查用的消火栓;
4. For buildings with indoor fire hydrants, if they are Flat roof, they should be equipped with fire hydrants for test and inspection on Flat roof;
5、高層工業(yè)建筑和水箱不能滿(mǎn)足不利點(diǎn)消火栓水壓要求的其他建筑,應在每個(gè)室內消火栓處設置直接啟動(dòng)消防水泵的按鈕,并應有保護設施。
5. For high-rise industrial buildings and other buildings where water tanks cannot meet the water pressure requirements of unfavorable point fire hydrants, buttons should be installed at each indoor fire hydrant to directly start the fire pump, and protective facilities should be provided.
That's all for the installation precautions of indoor fire hydrants. We hope they can provide you with good help. For more information, please visit our website http://m.guizhouhuli.net consulting service