1、消防水泵安裝前應校核產(chǎn)品合格證,以及其規格、型號和性能與設計要求應一致,并應根據安裝使用說(shuō)明書(shū)安裝;
1. Before installing the fire water pump, the product certificate should be verified, and its specifications, models, and performance should be consistent with the design requirements. It should be installed according to the installation and operation manual;
2、川消消防水泵安裝前應復核水泵基礎混凝土強度、隔振裝置、坐標、標高、尺寸和螺栓孔位置;
2. Before installing the Sichuan Fire Water Pump, the foundation concrete strength, vibration isolation device, coordinates, elevation, size, and bolt hole position of the pump should be reviewed;
3、消防水泵的安裝應符合現行標準《機械設備安裝工程施工及驗收通用規范》GB50231和《風(fēng)機、壓縮機、泵安裝工程施工及驗收規范》GB50275的有關(guān)規定;
3. The installation of fire water pumps should comply with the relevant provisions of the current national standards "General Code for Construction and Acceptance of Mechanical Equipment Installation Engineering" GB50231 and "Code for Construction and Acceptance of Fan, Compressor, and Pump Installation Engineering" GB50275;
4、消防水泵安裝前應復核消防水泵之間,以及消防水泵與墻或其他設備之間的間距,并應滿(mǎn)足安裝、運行和維護管理的要求;
4. Before installing the fire water pump, the spacing between the fire water pumps, as well as between the fire water pump and the wall or other equipment, should be reviewed and meet the requirements of installation, operation, and maintenance management;
川消
5、消防水泵吸水管上的控制閥應在消防水泵固定于基礎上后再進(jìn)行安裝,其直徑不應小于消防水泵吸水口直徑,且不應采用沒(méi)有可靠鎖定裝置的控制閥,控制閥應采用溝漕式或法蘭式閥門(mén);
5. The control valve on the suction pipe of the fire water pump should be installed after the fire water pump is fixed on the foundation. Its diameter should not be less than the diameter of the fire water pump suction port, and control valves without reliable locking devices should not be used. Control valves should be ditch or flange type valves;
6、當消防水泵和消防水池位于獨立的兩個(gè)基礎上且相互為剛性連接時(shí),吸水管上應加設柔性連接管;
6. When the fire pump and fire pool are located on two independent foundations and are rigidly connected to each other, a flexible connecting pipe should be added to the suction pipe;
7、吸水管水平管段上不應有氣囊和漏氣現象。變徑連接時(shí),應采用偏心異徑管件并應采用管頂平接;
7. There should be no air pockets or leaks on the horizontal section of the suction pipe. When connecting with variable diameter, eccentric reducing pipe fittings should be used and the top of the pipe should be flat connected;
8、消防水泵出水管上應安裝消聲止回閥、控制閥和壓力表;系統的總出水管上還應安裝壓力表和壓力開(kāi)關(guān);安裝壓力表時(shí)應加設緩沖裝置。壓力表和緩沖裝置之間應安裝旋塞;壓力表量程在沒(méi)有設計要求時(shí),應為系統工作壓力的2倍~2.5倍;
8. Silencing check valves, control valves, and pressure gauges should be installed on the outlet pipe of the fire pump; A pressure gauge and pressure switch should also be installed on the main outlet pipe of the system; When installing a pressure gauge, a buffer device should be added. A cock should be installed between the pressure gauge and the buffer device; When there is no design requirement, the range of the pressure gauge should be 2 to 2.5 times the working pressure of the system;
9、消防水泵的隔振裝置、進(jìn)出水管柔性接頭的安裝應符合設計要求,并應有產(chǎn)品說(shuō)明和安裝使用說(shuō)明。
9. The installation of the vibration isolation device and flexible joints of the inlet and outlet pipes of the fire water pump should meet the design requirements, and there should be product instructions and installation instructions.
消防水泵的安裝應符合相關(guān)的規定要求就講解到這里了,希望能夠給您好的幫助,更多事項就來(lái)我們網(wǎng)站http://m.guizhouhuli.net咨詢(xún)!
The installation of fire water pumps should comply with relevant regulations and requirements. That's all. We hope to provide you with good help. For more information, please come to our website http://m.guizhouhuli.net consulting service
上一篇:高壓細水霧滅火裝置還有哪些其它的選型?
下一篇:圖像型火災探測器怎么布線(xiàn)效率高

相關(guān)產(chǎn)品 / Related products

RM新时代投资官网
RM新时代手机版 RM新时代赚钱项目 RM新时代新项目-百度知道 RM新时代官方网站|首入球时间 新时代app游戏 rm新世界 RM新时代有限公司 rm新时代足球交易平台 RM新时代新项目-百度知道 rm理财